- PRODUCT
- Watt-hour Meters
- KEPCO Meters
High-voltage Industrial Watt-hour Meter
Dimensions
A-1 | A | B | C | D | |
---|---|---|---|---|---|
SIZE (mm) | 170 | 164 | 206 | 70 | 173 |
Parameters
Model | Phase·Wire | V | A | Hz | Pulse·kWh | Class |
---|---|---|---|---|---|---|
PS34CT005H05 | 3P4W | 110/190 | 5 (2.5) | 60 | 20,000 | 0.5 |
PS34CT005H10 | Grade 1.0 |
Features
-
Industrial Metering Data 1
Active Power Consumption, Lagging·Leading Reactive Power, Apparent Power, Maximum Demand Power, Power Factor -
Various External Control Signals Provided
Load Switching, EQI, and External Pulse Output Functions -
Industrial Rate Plan selectable
Time-of-Use(4 types of TOU) selection function, with precise built-in time and calendar -
Self-diagnosis and Event Information
Event Transmission Functions for Memory, Battery, Neutral Line Miswiring, Reverse Metering, Voltage Imbalance, etc. -
International Comm. Protocol
Metering data transmitted through KEPCO High-voltage Standard Protocol via Optical Communication Interface -
Improved Data Reliability
Power outage detection and battery monitoring functions prevent data loss during outages, and non-volatile memory ensures data retention for over 10 years -
Demand Management Data
Maximum Demand Power Block & Rolling Interval (1, 5, 10, 15, 30, 60 minutes), LP (Load Profile) -
Power Quality Information
Per-phase Voltage (V), Current (A), Phase Angle (º), THD (Total Harmonic Distortion), Frequency (Hz), Power Factor (PF)